CONTROL PANEL FEATURES
  • 8 Zones: 7 E.O.L. Supervised Programmable Zones: 6 Burglary, 1 Supervised Fire/Burglary/Aux, 1 Panic Zone.
  • 3 Modes of Programming:
    • Keypad Programming
    • Locally Downloadable from IBM Lap Top Computer (or equivalent) using Napco PCL2000 Local Downloading Cable and PCI2000 Software.
    • Remotely downloadable from IBM Personal Computer (or equivalent).
  • "Sensor Watch", An Exclusive Napco Feature--Reports Lack of Motion Detector Activity (per programmed time duration as a Day Zone Trouble (non-alarm condition).
  • Auto Download Utility (Uses PC Preset Utility in Standby Mode.)
  • Non-Volatile EEPROM Memory
  • Exit/Entry Follower Zone(s)
  • Chime by Zone-Selectable Duration, and 7 Segment Display of Chime Zone
  • 24-Hour Keypad Annunciation of Non-Alarm Zone (i.e., driveway alert)
  • Swinger Shut-Down by Zone
  • Progammable Output (PGM lug) for various applications
  • Remote Keypad Panic Zone
  • Programmable E.O.L. Resistor Disable Feature
  • Separate Dealer and User Program Codes
  • Flexible Watch Modes
  • Auto Bypass, Group Bypass, and Selectable Bypass
  • 2 Separately Programmable Entry Delay Times; 1 Programmable Exit Delay Time
  • Fire Response is Preprogrammed for Pulse Output
  • 3 Programmable Loop Response Times
  • 8 Stages of Lightning/Transient Protection
  • Extended Smoke Detector Reset Interval (reduces the chance of a second alarm if smoke has not cleared)
  • Resumes Previous Status After Power Outages
  • Watchdog Circuit
  • 24 Hour Automatic Battery Test
COMMUNICATOR FEATURES
  • Reports In All Major Formats Including BFSK and 4/2.
  • Optional Reporting of Bypass Zones.
  • Ability to Dial Touchtone Digit Labelled ("*" Key) To Disable "Call Waiting" For the Duration of The Call (not usable in all areas).
  • Opening and Closing Reports By User
  • Open Report After Alarm
  • Split, Double and Backup Reporting Capabilities
  • Rotary Dialing and Touchtone With Rotary Backup
  • Reports Alarm By Individual Zones
  • Conditional Closing Report With Status
  • 24-Hour Protection Programmable for All Zones
  • Communicator Confidence Test
  • Daily Test Timer (also resetable on any transmission)
  • Alarm and Restore Codes: on fire, fire trouble, low battery, and AC loss.

SPECIFICATIONS

  • Input Power: 16 VAC, Class 2 Step Down Transformer (TRF-8) (Supplied)
  • Alarm Outputs: Wet Output for Siren, Bell, etc. 12 VDC, 1A Maximum.
  • Combined Standby Current: Remote Power, Aux. Output, Relay Output 300mA Maximum With Supplied TRF8, Optional Higher Power TRF12 Transformer Yields 500mA Maximum.
  • Standby Time: See Energy Saver
  • Loop Resistance: 300 Ohms
  • Relay Contact Ratings: 24 VDC, 2A Resistive
  • Remote Station: Maximum Number: 5
  • Housing Dimensions: 10-3/8"H x 8-1/2"W x2-3/4"D
  • Shipping Weight: MA100Oe 9 lbs. MA1000e4 10.5 lbs.
KEYPAD FEATURES
  • 4-wire hookup
  • Sleek, Decorator Design in Classic White
  • Fire, Panic and Auxiliary Buttons plus Ambush Code.
  • Audible and Tactile Feedback when keys are pressed (programmable).
  • Up to 8 Arm/Disarm Codes Easily Changed by User
  • Unique Service Code--Which is Automatically Disabled When User One Returns and Arms/Disarms the Panel.
  • System Troubles Displayed at the Keypad: AC Fail, Low Battery, Fail- to-Communicate, Download Error
  • Arm Only Code
  • Alarm History
  • No Display of Bypass Zones While Armed
  • Pronounced LED Indication of All Bypassed Zones
  • Programmable Bypass Display Indicates Auto Bypassed or Priority- With-Bypass Zones
  • Separate Sounder Output
  • Fault Find--Facilitates Expedient Testing and Troubleshooting
  • Keypad Offset Time for 24 Hour Test
  • "Soft Touch" full-size keys

RP1054e Keypad:

  • Digital LED Zone Display
  • Concealed, Finger-Tip Zone/Usage Reference

RP1000eLCD Keypad:

  • Large, Backlit LCD Alphanumeric Zone Directory
  • Backlit Keys Brighten When Touched
  • Concealed, Finger-Tip Zone/Usage Reference